Inspection History Details
Inspection Status: Denied
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROVIDE WALKWAY AS PER 600.21 2. A SERVICE LIGHT PER 210.70 IS NEEDED 3. BOND LED LETTERS PER 600.7 4. A MARKING LABEL IS NEEDED 600.4 5. MAINTAIN WORKING CLEARANCES IN FRONT OF PANEL |