Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T07OT00821
Inspection Description - SIGN SHOP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2008 | SIGN SHOP | Approved | IVRS - Inspection :* OK SIGNS |
|
| 02/15/2008 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 02/13/2008 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* | |
| 12/27/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* 1) SUPPORT M/C CABLE ABOVE CEILING 2) BREAKER TO BE LISTED FOR USE BY MANUFACTURER 3) MAINTAIN WORKING CLEARANCES AT PANEL |
|
| 09/25/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MARKING LABELS NEEDED 600.4 2. WEATHERPROOF SLEEVING TO EXTEND INTO LETTER 3. VERIFY SIGN CIRCUIT PER 600.5 & 110.22 |
|
| 09/05/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 08/24/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection : CANCELLED |