Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 06/12/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* 1. PROTECT GTO CABLE FROM SHARP METAL EDGES AT PASS THROUGHS. 2. MAINTAIN HIGH VOLTAGE TO GROUNDED SURFACES CLEARANCES OK LETTER SETS |
|
| 05/30/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. TERMINATE FITTINGS 2. SEPARATE GROUND FROM GTO CABLE 3. RACEWAY BOND NOT UNDER TRANSFORMER MOUNTING SCREWS. 4. USE APPROVED FITTINGS WITH SEAL TIGHT 5. CHASE NIPPLES NOT APPROVED TO USE WITH COUPLING 6. MAINTAIN GTO CLEARANCES TO GROUNDED SURFACES AND OTHER CABLES 7. MARKING LABELS NEEDED 8. ISOLATE POWER TO SWITCH 9. TIGHTEN LOOSE FITTING 10. SUPPORT CONDUITS AT JUNCTION BOX INSIDE |