Permit: T07OT00805

Parcel: 136261290

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
06/29/2007 SIGN SHOP Approved IVRS - Inspection :*
06/26/2007 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. A MARKING LABEL IS NEEDED -- 600.4
2. FILL UNUSED OPENINGS IN LETTER WITH A NON-COMBUSTIBLE MATERIAL -- 110.12
3. PROVIDE ACCESS WALKWAY TO INSPECT -- 600.21
4. A SERVICE LIGHT IS NEEDED 210.70
5. SUPPORT SEAL TITE ON ROOF
6. PROPER GROUNDING IS NEEDED TO TRANSFORMER
7. FILL UNUSED OPENING IN BACK OF JUNCTION BOX ON ROOF
8. SWITCH TO BE AS PER 600.6
9. REVISE PLANS FOR ADDED TRANSFORMER
10. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR.