Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T07OT00805
Inspection Description - SIGN SHOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/29/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
06/26/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. A MARKING LABEL IS NEEDED -- 600.4 2. FILL UNUSED OPENINGS IN LETTER WITH A NON-COMBUSTIBLE MATERIAL -- 110.12 3. PROVIDE ACCESS WALKWAY TO INSPECT -- 600.21 4. A SERVICE LIGHT IS NEEDED 210.70 5. SUPPORT SEAL TITE ON ROOF 6. PROPER GROUNDING IS NEEDED TO TRANSFORMER 7. FILL UNUSED OPENING IN BACK OF JUNCTION BOX ON ROOF 8. SWITCH TO BE AS PER 600.6 9. REVISE PLANS FOR ADDED TRANSFORMER 10. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR. |