Permit: T07OT00718

Parcel: 136406780


Addresses:

9630 E 22ND ST #110

Inspection Status: Approved

Inspection History: SIGN SHOP

Date Description Inspector Results Comments
05/15/2007 SIGN SHOP Approved IVRS - Inspection :*
05/11/2007 SIGN SHOP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) MARKING LABELS ARE NEEDED 600.4
2) MAINTAIN GTO TO GROUNDED SURFACES 1 1/2"
3) GROUND JUNCTION BOX
4) SUPPORT M/C CABLE AS PER CODE 12" + 6'
5) SWITCH IF NOT WITHIN SIGHT TO BE CAPABLE OF BEING LOCKED OUT
6) USE TERMINAL ENDS WITH STRANDED CONDUCTORS TO TERMINATE AT SCREWS
7) A SERVICE LIGHT IS NEEDED 210.70
8) USE CONNECTORS LISTED FOR M/C CABLE
9) SUPPORT FLEX LONGER THAN 4' AS PER CODE 12" + 4'
10) NEED CITY STICKERS-INSPECTOR TO INSTALL
11) DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR