Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T07OT00718
Inspection Description - SIGN SHOP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/15/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 05/11/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MARKING LABELS ARE NEEDED 600.4 2) MAINTAIN GTO TO GROUNDED SURFACES 1 1/2" 3) GROUND JUNCTION BOX 4) SUPPORT M/C CABLE AS PER CODE 12" + 6' 5) SWITCH IF NOT WITHIN SIGHT TO BE CAPABLE OF BEING LOCKED OUT 6) USE TERMINAL ENDS WITH STRANDED CONDUCTORS TO TERMINATE AT SCREWS 7) A SERVICE LIGHT IS NEEDED 210.70 8) USE CONNECTORS LISTED FOR M/C CABLE 9) SUPPORT FLEX LONGER THAN 4' AS PER CODE 12" + 4' 10) NEED CITY STICKERS-INSPECTOR TO INSTALL 11) DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR |