Inspection History Details
Inspection Status: Partial Approval
Inspection History: SIGN SHOP
Permit Number - T07OT00661
Inspection Description - SIGN SHOP
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* | |
04/23/2007 | SIGN SHOP | Approved | IVRS - Inspection :* OK OUTSIDE SIGNS RECEIVED CHECK #604443141 --- $108.00 |
|
04/20/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SWITCH TO BE CAPABLE TO BE LOCKED OUT 2. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING - BOXES AND LETTERS 3. USE TERMINAL END FOR STRANDED CONDUCTORS - BOXES AND LETTERS 4. WE HAVE CONDUCTOR BOX OVERFILL 5. BOND JUNCTION BOX WITH GROUNDING EQUIPMENT CONDUCTOR 6. USE AN APPROVED CABLE CONNECTOR AT LETTERS 7. ISOLATE POWER TO SWITCH FOR PRIMARY CONDUCTORS MENU BOARD 8. BOND HAND HOLE POLE SIGN ABOVE COUNTER: 1. WHERE IS PK TAKE UP 2. BOND PK HOUSING FOR GROUND PATH 3. SWITCH TO BE CAPABLE OF BEING LOCKED OUT 4. SECURE PK HOUSINGS 5. SUPPORT FLEX CONDUITS 6. TIGHTEN LOOSE FITTINGS |
|
04/13/2007 | SIGN SHOP | Denied | THE WIRING IS NOT COMPLETE OR DOES NOT COMPLY WITH CODE. BOND LED LETTERS 600.7 |