Inspection Status: Denied
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2007 | FIRE - FINAL | Denied | 1. Plans do not reflect what is on site, need plans to show changes; a. video arcade room is now a office and outside door added b. wall added blocking exit sign to rear exit in store c. outside patio added on north end 2. Add power/battery back up exit sign to wall for rear exit door in store 3. Remove security door from rear exit in kitchen egress doors need to open outward. 4. Need up to date inspection on fire extinguisher system on hood system. 5. Extension cords not allowed as perment wiring remove cord to register in restaurant. 6. Need to install fire department key box system for access through security bars on egress doors. |