Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T07OT00566
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/30/2007 | FIRE - FINAL | Approved | ||
04/11/2007 | FIRE - FINAL | Denied | IFC 605.5 EXTENSION CORDS 1. WHITE EXTENSION CORD ON FRONT SALES FLOOR NOT ALLOWED, CAN NOT WALK ON CORDS 2. ORANGE EXTENSION CORD BACK WORK AREA NOT ALLOWED. CAN NOT WALK ON CORDS 3. GRAY EXTENSION CORD BACK WALL IN WORK ROOM NOT ALLOWED IFC 1008.1.8.3 LOCKS AND LATCHES LABEL FRONT DOOR WITH THE FOLLOWING: "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" LETTERS SHALL BE 1 INCH HIGH. FRONT ENTRANCE SECURITY DOOR SHALL HAVE A THUMB LATCH NOT DOULBE CYLINDER KEYED DEAD BOLT. |