Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 05/06/2007 | SIGN SHOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE OF 600V TERMINAL ENDS ON 15KV CABLE NOT ALLOWED 2. MAINTAIN GTO TO GROUNDED SURFACES FOR CLEARANCES 1 1/2" |