Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T07OT00417
Inspection Description - SIGN SHOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/05/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
06/01/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1. ISOLATE PRIMARY CONDUCTOR TO SWITCH 2. MAINTAIN GTO TO GROUNDED SURFACES 1 1/2" 3. SUPPORT M/C CABLE AS PER CODE 12" & 6' 4. MISSING JUNCTION BOX COVER 5. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR. |
|
05/14/2007 | SIGN SHOP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO PLANS OR PERMIT ON SITE 2. PLEASE HAVE SIGN CONTRACTOR PRESENT TO PROVIDE ACCESS AND OPEN UP SIGN FOR INSPECTION. |