Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
Permit Number - T07OT00413
Inspection Description - SIGN SHOP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 07/11/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* 1. SWITCHES TO BE LOCKABLE 2. CHECK WITH PERMITTING 791-5550 "0" PERMIT COUNTER |
|
| 06/07/2007 | SIGN SHOP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SIGN CIRCUIT TO BE AS PER 600.5 -- LED NEEDS TO BE ON DIFFERENT CIRCUIT 2. TIGHTEN LOOSE CONDUIT FITTINGS & SUPPORT BOXES 3. SUPPORT SEAL TITE OVER 4' IN LENGTH 4. SWITCHES NOT WITHIN SITE OF SIGN TO BE CAPABLE OF BEING LOCKED OUT - ISOLATE PRIMARY CONDUCTORS TO SWITCH -- 600.6 5. CANNOT USE SHEETMETAL SCREWS FOR GROUNDING 6. CANNOT USE 600V TERMINAL ENDS ON 15KV WIRE 7. A SEPARATE ELECTRICAL PERMIT IS NEEDED FOR AWNING LED'S |
|
| 04/30/2007 | SIGN SHOP | Denied | IVRS - Inspection : There is no access to the site.| 920* 1. SIGN CONTRACTOR TO BE PRESENT TO ACCESS & OPEN SIGNS FOR INSPECTION. 2. PLANS & PERMIT TO BE ON SITE |