Inspection History Details
Inspection Status: Approved
Inspection History: CERTIFICATE OF OCCUPANCY
Permit Number - T07OT00334
Inspection Description - CERTIFICATE OF OCCUPANCY
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2007 | CERTIFICATE OF OCCUPANCY | Approved | IVRS - Inspection :* | |
02/16/2007 | CERTIFICATE OF OCCUPANCY | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE DEADBOLTS FROM DOORS WITH PANIC HARDWARE 2. POST SIGNS AT FRONT EXITS "THIS DOOR TO REMAIN UNLOCKED WHILE BUILDING IS OCCUPIED" 3. LABEL ELECTRIC PANEL 4. ALL ELECTRIC OUTLETS TO BE PROPERLY COVERED 5. REPAIR CEILING OVER ICE MACHINE 6. HOOD EXTINGUISHING SYSTEM TO BE RECERTIFIED 7. ALL INDIRECT WASTE TO TERMINATE 1" ABOVE FLOOR DRAINS 8. REDUCED PRESSURE BACKFLOW ASSEMBLY REQUIRED FOR CARBONATOR. MUST BE CERTIFIED. |