Permit: T07OT00204

Parcel: 131070540

Inspection Status: Approved

Inspection History: SIGN SHOP

Permit Number - T07OT00204

Inspection Description - SIGN SHOP

Inspection Status - Approved

Date Description Inspector Results Comments
06/26/2008 SIGN SHOP Approved IVRS - Inspection :*
06/29/2007 SIGN SHOP Partial Approval IVRS - Inspection :*
OK LETTER SETS & CABINETS
1. NEED WALKWAY TO LAST SERVICABLE POWER
SUPPLY -- 600.21
2. A SERVICE LIGHT IS NEEDED -- 210.70
3. LED PLANS NOT REFLECTIVE OF INSTALLED LETTERS.