Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2007 | SIGN SHOP | Approved | IVRS - Inspection :* | |
| 05/03/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* OK SIGNS 1. NEED CITY PAPERWORK & STICKERS |
|
| 03/13/2007 | SIGN SHOP | Not ready for Inspection | IVRS - Inspection :* 1. FINISH PREVIOUS ITEMS AND CHECK ON SITE 2. DO NOT ENERGIZE SIGN UNTIL FINALED BY ELECTRICAL INSPECTOR. |
|
| 02/28/2007 | SIGN SHOP | Partial Approval | IVRS - Inspection :* 1. SUPPORT GTO CABLE IN RACEWAY 2. USE OF 600V TERMINAL END ON 1500V CABLE NOT LISTED FOR OR ALLOWED. 3. SEPARATE PRIMARY AND SECONDARY CONDUCTORS IN RACEWAY 4. MAINTAIN GTO CLEARANCES |