Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. IMPROPER SPLICE AT RECEPTACLE WIRING ABOVE REFRIG. 2. TIMER SWITCH NOT GROUNDED 3. ROMEX ENTRY INTO SWITCH WRONG, NEEDS ROMEX CONNECTORS 4. GROUNDS AND NEUTRALS CANNOT BE CONNECTED 5. METAL COVER ABOVE SW BOX (CIRCUIT BREAKERS) NEEDS PLASTIC BUSHING 6. THE WIRING ON THIS MH HAS BEEN ALTERED 7. SINCE MH HAS BEEN RELOCATED IT REQUIRES A STATE OF ARIZONA MH INSPECTION IN ORDER TO CLEAR FOR POWER & GAS |
|
| 09/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) #10 CONUCTORS TO BE COLOR CODED PER NEC-GROUND GREEN, NEUTRAL-WHITE, MUST CONTINOUS 2) SUPPORT PVC CONDUIT AT PEDESTAL TERMINATION, MUST BE SCH 80 FOR EXPOSED ABOVE GROUND 3) USE PROPER TERMINAL TO GOUND STRANDED WIRE IN J-BOX AT M.H. 4) UNIT MUST BE OPEN FOR INSPECTION BE SURE THERE ARE SMOKE DETECTORS IN HALLWAY AND SLEEPING AREAS, GFI PROTECTED OUTLETS IN KITCHEN SINK AND BATHROOM SINK AREAS, RECALL INSPECTION WHEN READY |