Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 11/05/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ONE HOME AGAIN IF OWNER CANNOT BE HOME CONTRACTOR SHOULD BE PRESENT. |
|
| 10/30/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE RESCHEDULE WHEN SOMEONE WILL BE HOME |
|
| 10/29/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONDENSATE HOSE KINKED. SECURE DRAIN LINE IN CLOSET RELOCATE FROM IN FRONT OF WATER HEATER. 2. RELOCATE CONDENSATE PUMP TO OTHER SIDE OF FURNACE 3. PROVIDE MIN. 3 SCREWS IN ALL JOINTS IN VENT CONNECTOR 4. CIRCUIT BREAKER NOT SIZED PER DATA PLATE 5. PROVIDE A COVER ON LB USED IN LOW VOLTAGE CONDUIT SEAL OPENING IN WALL 6. DO NOT PUT 2 WIRES ON 1 LUG IN ELEC. DISCONNECT. USE AN APPROVED METHOD FOR CONNECTING SURGE PROTECTOR |