Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/29/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 10/17/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - CONDENSATE CANNOT TERMINATE INTO A SEWER VENT - TURN DISCONNECT 180 DEG. TO ALLOW ADEQUATE ACCESS - PROVIDE A GFI SERVICE RECEPTACLE ON ROOF WITH WATERPROOF BUBBLE TYPE COVER. - PROVIDE MIN. 2" R8 DUCT LINER IN EXPOSED DUCT ON ROOF - INSULATE ALL DUCT IN THE ATTIC WITH R8 INSULATION W/VAPOR BARRIER - FLEX DUCT TO BE MIN. R8 - PROVIDE ADEQUATE COMBUSTION AIR FOR WATER HEATER |