Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 11/29/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* THIS WORK IS A NEW UNIT INSTALLED ON A ROOF FIRST TIME. PROVIDE REQUIRED DRAWING APPROVED BY CITY OF TUCSON |
|
| 10/22/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE THE PROPER DESCRIPTION OF WORK & SUBMIT REQUIRED DRAWING WITH STRUCTURAL LOAD CALCULATIONS APPROVED BY THE CITY OF TUCSON 2. CAP OFF UNUSED FURNACE VENT WITH SHEETMETAL 3. 3/8" I.D GAS FLEX NOT ADEQUATE FOR 120,000 BTU |