Permit: T07ME00688

Parcel: 134240610


Addresses:

6441 E ELI DR


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07ME00688

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/24/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
11/29/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
THIS WORK IS A NEW UNIT INSTALLED ON A ROOF FIRST TIME.
PROVIDE REQUIRED DRAWING APPROVED BY CITY OF TUCSON
10/22/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE THE PROPER DESCRIPTION OF WORK & SUBMIT REQUIRED DRAWING WITH STRUCTURAL LOAD CALCULATIONS APPROVED BY THE CITY OF TUCSON
2. CAP OFF UNUSED FURNACE VENT WITH SHEETMETAL
3. 3/8" I.D GAS FLEX NOT ADEQUATE FOR 120,000 BTU