Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07ME00679
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/18/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - CIRCUIT BREAKER ON ROOF STILL OVERSIZED - CONDUCTORS STILL NOT PROPERLY IDENTIFIED - THERE IS WHITE WIRE USED FOR GROUND - RUN NEW WIRE TO THE SERVICE RECEPTACLE WITH PROPER COLORS - 100 PSI TEST IS OK FOR GAS LINE TO FURNACE - NEED ACCESS INSIDE HOUSE TO CHECK FOR PROPER FLEX DUCTS INSULATION R VALUE |
|
| 10/05/2007 | MECHANICAL - FINAL | Denied | - SECURE THE ANGLE IRON STAND TO THE ROOF - DO NOT USE FOIL TAPE TO SEAL THE GAS LINE ROOF JACK - PROVIDE THE PROPER COLOR CONDUCTORS USED FOR SERVICE RECEPTACLE. - THE CIRCUIT BREAKER IN THE DISCONNECT ON ROOF IS OVERSIZED 35 AMP IS MAX - ID CIRCUIT BREAKER IN PANEL. - PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPING TO FURNACE - ALL NEW FLEX DUCT IN THE ATTIC MUST BE MIN. R-8 |