Permit: T07ME00679

Parcel: 122090770


Addresses:

3973 E JUSTIN LN


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07ME00679

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/26/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/18/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- CIRCUIT BREAKER ON ROOF STILL OVERSIZED
- CONDUCTORS STILL NOT PROPERLY IDENTIFIED
- THERE IS WHITE WIRE USED FOR GROUND
- RUN NEW WIRE TO THE SERVICE RECEPTACLE WITH
PROPER COLORS
- 100 PSI TEST IS OK FOR GAS LINE TO FURNACE
- NEED ACCESS INSIDE HOUSE TO CHECK FOR PROPER FLEX DUCTS INSULATION R VALUE
10/05/2007 MECHANICAL - FINAL Denied - SECURE THE ANGLE IRON STAND TO THE ROOF
- DO NOT USE FOIL TAPE TO SEAL THE GAS LINE ROOF JACK
- PROVIDE THE PROPER COLOR CONDUCTORS USED FOR SERVICE RECEPTACLE.
- THE CIRCUIT BREAKER IN THE DISCONNECT ON ROOF IS OVERSIZED 35 AMP IS MAX
- ID CIRCUIT BREAKER IN PANEL.
- PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPING TO FURNACE
- ALL NEW FLEX DUCT IN THE ATTIC MUST BE MIN. R-8