Permit: T07ME00653

Parcel: 133460670

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/17/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
125 PSI TEST IS OK
10/11/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLEASE SCHEDULE AN INSPECTION WHEN SOMEONE WILL BE HOME -- THERE WAS NO MESSAGE
10/05/2007 MECHANICAL - FINAL Denied SUCTION LINE LEAKING IN FAN COIL COMPARTMENT
LINE SET MAY NEED A P-TRAP TO GET THE OIL BACK UP TO THE COMPRESSOR. REPAIR LEAK & PROVIDE A MIN. 100 LB PRESSURE TEST ON ENTIRE LINE SET.
10/04/2007 MECHANICAL - FINAL Cancelled IVRS - RI canceled
09/27/2007 MECHANICAL - FINAL Denied - PROVIDE A TRAP ON CONDENSATE DRAIN LINES AS PER INSTALL INSTRUCTIONS. PROVIDE A SECONDARY OVERFLOW SENSOR
- SUPPORT REFER LINES UP OFF OF CEILING
- DO A BETTER JOB SEALING AROUND REFER LINE PENETRATING THE ROOF
- INSULATE ALL OF THE SUCTION LINE NOT ABOVE DRAIN PAN
09/25/2007 MECHANICAL - FINAL Cancelled IVRS - RI canceled