Permit: T07ME00649

Parcel: 123121640


Addresses:

1421 E EDISON ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07ME00649

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/31/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE GAS PRESSURE TEST (CAN SMELL GAS ON ROOF)
2. PROVIDE DIRT LEG ON GAS PIPING
3. CONDENSATE NOT TERMINATED IN APPROVED LOCATION
4. PROVIDE ELECTRICAL PERMIT
5. PROVIDE PROPER SUPPORT FOR UNIT (SUPPORTS RUN PARALLEL TO TRUSS)
6. PROVIDE R-8 INSULATION IN ALL EXTERIOR DUCT WORK
7. POWER WIRING TO OLD COOLER NOT PROPERLY TERMINATED