Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/15/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* ELEC. INSPECTOR WILL CONFIRM PROPER BREAKER |
|
| 10/10/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE A ROOF JACK AT CONDENSATE DRAIN USE ONLY A SIEMENS BREAKER FOR CONDENSOR |
|
| 09/13/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE A TRAP ON THE PRIMARY DRAIN AND AN OVERFLOW SENSOR ON SECONDARY 2. DO NOT CUT THE PLUG OFF OF THE CONDENSATE PUMP. REMOVE FUSE STAT & PROVIDE A RECEPTACLE FOR THE PUMP 3. TIGHTEN THE ROMEX CONNECTOR ONTO THE FURNACE CORD 4. USE ONLY A SIEMENS BREAKER 5. PROVIDE A GFI SERVICE RECEPTACLE ON THE ROOF 6. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. BLOCK & CLAMP COPPER TUBING EVERY 6' 7. PROVIDE A PERMIT & INSPECTION FOR SERVICE UPGRADE |
|
| 09/11/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SCHEDULE AN INSPECTION WHEN SOMEONE (AN ADULT) WILL BE PRESENT |