Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 09/24/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - PROVIDE A TRAP ON PRIMARY DRAIN LINE - PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET - PROVIDE A ROOF JACK AT ELEC. PENETRATION - PROVIDE A GFI SERVICE RECEPTACLE WITH A WATERPROOF BUBBLE TYPE COVER - PROPERLY IDENTIFY CONDUCTORS USED FOR CONDENSOR - SUPPORT COPPER DRAIN LINE ON ROOF EVERY 6' |
|
| 09/13/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |