Permit: T07ME00627


Addresses:

2771 E AIRPORT DR


Inspection Status: Denied

Inspection History: MECHANICAL - HOODS

Permit Number - T07ME00627

Inspection Description - MECHANICAL - HOODS

Inspection Status - Denied

Date Description Inspector Results Comments
09/11/2007 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*
REMOVE ALL UNAPPROVED INSULATION FROM GREASE DUCT
PROVIDE CLEANOUTS AT BOTH ENDS OF GREASE DUCT
USE ONLY APPROVED FIRE WRAP
PROVIDE A MECHANICAL PERMIT & SCHEDULE ON INSPECTION PRIOR TO INSTALLING FIRE WRAP.
THE HOOD & EXHAUST FAN ARE OK
08/31/2007 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*