Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 11/15/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ALL DUCT SYSTEMS IN EXTERIOR APPLICATIONS ARE TO BE INSULATED WITH A MINIMUM OF R-8 PER 403.2.1 ENERGY CONSERVATION CODE 1" DUCT LINER IS ONLY EQUAL TO R-4.2 |
|
| 09/27/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* MUST PROVIDE FUSED DISCONNECT PER MANUFACTURER NAME PLATE |