Permit: T07ME00614

Parcel: 106122420


Addresses:

1502 W KILBURN ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/04/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/15/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
ALL DUCT SYSTEMS IN EXTERIOR APPLICATIONS ARE TO BE INSULATED WITH A MINIMUM OF R-8 PER 403.2.1 ENERGY CONSERVATION CODE
1" DUCT LINER IS ONLY EQUAL TO R-4.2
09/27/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
MUST PROVIDE FUSED DISCONNECT PER MANUFACTURER NAME PLATE