Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/25/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. CONDENSATE PIPE NOT PAINTED 2. NO GFI ON ROOF 3. MECHANICAL CONTRACTOR TO BE PRESENT ON NEXT INSPECTION TO VERIFY 2" INSULATION ON ROOF (BRING SHEETMETAL TOOLS & MATERIAL TO PATCH DUCT WORK) |
|
| 09/21/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PAINT CONDENSATE LINE PVC SECURE CONDENSATE LINE INSULATE DUCT MIN. R-8 BUBBLE COVER SERVICE GFCI |
|
| 09/18/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PAINT CONDENSATE PVC 2) SECURE EVERY 4' 3) SERVICE OUTLET WITHIN 25' REQUIRED 4) PROVIDE SHIELDED CANVAS OVER CONNECTORS |
|
| 09/14/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - SUPPORT CONDENSATE EVERY 4' & PAINT W/LATEX PAINT - SECURE LOW VOLTAGE CONDUIT - PROVIDE A GFI SERVICE RECEPTACLE ON ROOF W/WATERPROOF BUBBLE TYPE COVER - PROVIDE A SHIELD OVER CANVAS CONNECTORS - 3/8" X 18" GAS FLEX NOT ADEQUATE FOR 100,000 BTU - PROVIDE MIN. 2" R8 DUCT LINER IN EXPOSED DUCT ON ROOF |