Permit: T07ME00610

Parcel: 13818028A


Addresses:

7112 S 6TH AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/28/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/25/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. CONDENSATE PIPE NOT PAINTED
2. NO GFI ON ROOF
3. MECHANICAL CONTRACTOR TO BE PRESENT ON NEXT INSPECTION TO VERIFY 2" INSULATION ON ROOF (BRING SHEETMETAL TOOLS & MATERIAL TO PATCH DUCT WORK)
09/21/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PAINT CONDENSATE LINE PVC
SECURE CONDENSATE LINE
INSULATE DUCT MIN. R-8
BUBBLE COVER SERVICE GFCI
09/18/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PAINT CONDENSATE PVC
2) SECURE EVERY 4'
3) SERVICE OUTLET WITHIN 25' REQUIRED
4) PROVIDE SHIELDED CANVAS OVER CONNECTORS
09/14/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- SUPPORT CONDENSATE EVERY 4' & PAINT W/LATEX PAINT
- SECURE LOW VOLTAGE CONDUIT
- PROVIDE A GFI SERVICE RECEPTACLE ON
ROOF W/WATERPROOF BUBBLE TYPE COVER
- PROVIDE A SHIELD OVER CANVAS CONNECTORS
- 3/8" X 18" GAS FLEX NOT ADEQUATE FOR 100,000 BTU
- PROVIDE MIN. 2" R8 DUCT LINER IN EXPOSED DUCT ON ROOF