Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*CORRECTIONS HAVE BEEN MADE | |
| 09/24/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* CORRECTIONS HAVE NOT BEEN MADE |
|
| 09/06/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - COVER THE CANVAS CONNECTORS WITH SHEETMETAL - CSST GAS PIPE ON ROOF RUBBER COATING RIPPED & NOT PER INSTALL INSTRUCTIONS . - REPLACE CSST GAS LINE & RETEST - CONDENSATE DRAIN NOT INSTALLED PER CODE - LOW VOLTAGE WIRING MUST BE IN CONDUIT - SECURE THE ANGLE IRON STAND TO THE ROOF - DISCONNECT OVERFUSED - SECURE ELEC. CONDUIT AT CIRCUIT PANEL - I.D CIRCUIT BREAKER - USE ONLY A G.E BREAKER - PROVIDE A GFI SERVICE RECEPTACLE ON ROOF. |