Permit: T07ME00596

Parcel: 127081810


Addresses:

5418 E 10TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/09/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
SECURE PUMP DRAIN IN FURNACE CLOSET
09/27/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PLUG CONDENSATE PUMP INTO A RECEPTACLE
- FUSE STAT IS NOT REQUIRED FOR FURNACE
- PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN
- SECURE PUMP DRAIN IN CLOSET
- INSULATE SHEETMETAL DUCT ABOVE EVAP COIL
- CONDENSATE CANNOT TERMINATE INTO A SEWER VENT
- SUPPORT COPPER DRAIN LINE EVERY 6'
- LOW VOLTAGE WIRE MUST BE IN CONDUIT OR PROTECTED FROM PHYSICAL DAMAGE
- ELEC SERVICE NOT TO CODE. NUMEROUS VIOLATIONS PLEASE LEAVE ELEC. CONTRACTOR OBTAIN ELEC. PERMIT FOR WORK TO BE DONE
- PROVIDE HOSE CLAMPS ON PUMP DRAINS