Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE SECURE PUMP DRAIN IN FURNACE CLOSET |
|
| 09/27/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PLUG CONDENSATE PUMP INTO A RECEPTACLE - FUSE STAT IS NOT REQUIRED FOR FURNACE - PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN - SECURE PUMP DRAIN IN CLOSET - INSULATE SHEETMETAL DUCT ABOVE EVAP COIL - CONDENSATE CANNOT TERMINATE INTO A SEWER VENT - SUPPORT COPPER DRAIN LINE EVERY 6' - LOW VOLTAGE WIRE MUST BE IN CONDUIT OR PROTECTED FROM PHYSICAL DAMAGE - ELEC SERVICE NOT TO CODE. NUMEROUS VIOLATIONS PLEASE LEAVE ELEC. CONTRACTOR OBTAIN ELEC. PERMIT FOR WORK TO BE DONE - PROVIDE HOSE CLAMPS ON PUMP DRAINS |