Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* USE ONLY A HEAT STRIP LISTED FOR USE WITH THIS UNIT. DO NOT WRITE IN FUSING REQUIREMENTS WITH A MAGIC MARKER |
|
| 09/06/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - PROVIDE A ROOF JACK AT CONDENSATE DRAIN - BLOCK & CLAMP DRAIN ON ROOF - DO NOT TERMINATE ONTO THE SIDEWALK - IF ADDING A HEAT STRIP THE #8 WIRE FROM CIRCUIT BREAKER WILL NOT BE ADEQUATE |
|
| 08/30/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* PLEASE SCHEDULE AN INSPECTION WHEN SOMEONE WILL BE HERE 8 AM |