Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
Permit Number - T07ME00581
Inspection Description - MECHANICAL - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2007 | MECHANICAL - FINAL | Partial Approval | PROVIDE A PERMIT FOR ELEC. UPGRADE EVERYTHING ELSE IS OK |
|
09/14/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE MIN. 3 SCREWS IN ALL JOINTS OF VENT CONNECTOR - DO NOT CUT THE PLUG OFF OF THE CONDENSATE PUMP - FUSE STAT IS NOT REQUIRED - PROVIDE A RECEPTACLE FOR PUMP CORD - LOW VOLTAGE WIRE MUST BE PROTECTED FROM PHYSICAL DAMAGE AT CONDENSOR - TAPE WHITE WIRE IN DISCONNECT WITH BLACK TAPE AT BOTH ENDS - I.D CIRCUIT BREAKER - USE A WATERPROOF FITTING ON TOP OF ELEC. PANEL - PROVIDE A PERMIT FOR ELEC. UPGRADE |
|
08/29/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |