Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/27/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/10/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THIS A/C UNIT REQUIRES A DUAL POWER SUPPLY. ONE FOR THE HEAT STRIP AND ONE FOR THE A/C. MARK UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALLED AND FROM EACH COMPONENT AS PER DATA PLATE 2) PROVIDE A TRAP ON CONDENSATE DRAIN. BLOCK AND CLAMP PVC EVERY 4'. TERMINATE WITHIN 6" OF THE GROUND WITH AN ELBOW AND NIPPLE. SECURE PVC TO THE HOUSE 3) PROVIDE A ROOF JACK AT ELECTRIC CONDUIT. PROVIDE GFI SERVICE RECEPTACLE ON ROOF 4) PROVIDE MIN R8-2" DUCT LINES IN EXPOSED DUCT ON ROOF. COVER ALL OF THE CANVAS CONNECTOR. PROVIDE ADEQUATE SUPPORT FOR DUCT ON ROOF 5) NEED TO SEEE WHERE OLD FURNACE WAS REMOVED 6) SUPPORT LOW VOLTAGE ELECTRIC CONDUIT ON ROOF 7) PROVIDE A PERMIT FOR ELECTRIC PANEL UPGRADE |