Permit: T07ME00547

Parcel: 138230620


Addresses:

617 W CALLE RITA

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/30/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
10 PSI TEST IS OK
08/24/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONDENSATE LINE IS STILL FLAT. TRAP IS BACKWARDS.
OUTLET ON TRAP IS HIGHER THAN OUTLET ON UNIT
GAS LINE NOT HOLDING PRESSURE
TURN OFF SHUTOFF VALVE AT UNIT
08/13/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- CAP OFF OLD GAS LINE TO FURNACE
- PROVIDE MIN. 1/8" PER FT. SLOPE ON DRAIN LINE
- PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPING
- RECONNECT AT METER WITH A UNION
- PROVIDE A GFI SERVICE RECEPTACLE ON THE ROOF WITH A BUBBLE TYPE COVER.