Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 10 PSI TEST IS OK |
|
| 08/24/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CONDENSATE LINE IS STILL FLAT. TRAP IS BACKWARDS. OUTLET ON TRAP IS HIGHER THAN OUTLET ON UNIT GAS LINE NOT HOLDING PRESSURE TURN OFF SHUTOFF VALVE AT UNIT |
|
| 08/13/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - CAP OFF OLD GAS LINE TO FURNACE - PROVIDE MIN. 1/8" PER FT. SLOPE ON DRAIN LINE - PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPING - RECONNECT AT METER WITH A UNION - PROVIDE A GFI SERVICE RECEPTACLE ON THE ROOF WITH A BUBBLE TYPE COVER. |