Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07ME00503

Parcel: 126191740


Addresses:

4456 E 18TH ST


Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Permit Number - T07ME00503

Inspection Description - MECHANICAL - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
07/19/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
120,000 BTU FURNACE 100' FROM METER REQUIRES 1" GAS PIPE. SEE PLUMBING CODE FOR PROPER SIZING. PROVIDE A GAS SHUT OFF VALVE ON ROOF AT THE FLEX CONNECTOR.
PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPING