Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 120,000 BTU FURNACE 100' FROM METER REQUIRES 1" GAS PIPE. SEE PLUMBING CODE FOR PROPER SIZING. PROVIDE A GAS SHUT OFF VALVE ON ROOF AT THE FLEX CONNECTOR. PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPING |