Permit: T07ME00503

Parcel: 126191740


Addresses:

4456 E 18TH ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/19/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
120,000 BTU FURNACE 100' FROM METER REQUIRES 1" GAS PIPE. SEE PLUMBING CODE FOR PROPER SIZING. PROVIDE A GAS SHUT OFF VALVE ON ROOF AT THE FLEX CONNECTOR.
PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPING