Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/16/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/12/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FE PLASTIC THREADS ARE NOT ACCEPTABLE W/A MALE METALLIC THREAD.
2. PAINT EXPOSED PLASTIC
3. SEDIMENT TRAP REQUIRED ON NEW GAS APPLIANCE

SEE GAS INSPECTION T07PL01192 FOR LIST OF GAS PIPING CONNECTIONS.
07/09/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE A GFI SERVICE RECEPTACLE W/WATERPROOF COVER
3/8" I.D X 18" GAS FLEX NOT ADEQUATE FOR 100,000 BTU
PROVIDE ROOF JACKS AT ROOF PENETRATIONS