Permit: T07ME00445

Parcel: 107120640

Inspection Status: Not ready for Inspection

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/23/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
07/02/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN
OUTLET ON COIL.
- DO NOT TAKE THE PLUG OFF OF THE CONDENSATE PUMP
- INSULATE THE UNINSULATED SLEEVE IN FURNACE ROOM
- PROVIDE HOSE CLAMPS ON CONDENSATE PUMP HOSE
06/20/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) A/C UNIT NEEDS VENTED TRAP
2) DRAIN LINE CANNOT BE DRAINED INTO A ROOF VENT NEEDS TO TERMINATE OUTSIDE ON GROUND CONDENSATE DISPOSAL M1411.3
3) NEED TO SECURE INSULATED LINES AT AIR HANDLER