Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 05/22/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 20 AMP. FUSES ARE NOT ADEQUATE FOR A 10KW HEAT STRIP ELEC. CONNECTION TO A/C UNIT IS LOOSE. 2. GFI SERVICE RECEPTACLE NOT WIRED CORRECTLY. 3. CIRCUIT TESTER SAYS "OPEN GROUND" |
|
| 07/03/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE YOUR CONTRACTOR GET A NEW PERMIT WITH THE PROPER DESCRIPTION OF WORK. A 2.5 TONE HEAT PUMP WAS NOT REPLACED. AN EXISTING FURNACE WAS REMOVED AND A NEW A/C UNIT WAS INSTALLED WITH A NEW ELEC. CIRCUIT. 2. PROVIDE MIN. R8 DUCT LINER IN EXPOSED DUCT ON ROOF 3. THE OUTLET ON THE CONDENSATE TRAP IS HIGHER THAN THE OUTLET ON THE AC UNIT 4. WHAT SIZE HEAT STRIP WAS INSTALLED? I.D DATA PLATE 5. PROVIDE A GFI SERVICE RECEPTACLE ON ROOF 6. NEED TO SEE CIRCUIT BREAKER |