Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/17/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE OVERFLOW SENSOR ON SECONDARY DRAIN OUTLET ON COIL |
|
| 06/28/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSULATE SHEETMETAL DUCT ABOVE EVAP. COIL 2. PROVIDE MIN. 3 SCREWS IN ALL JOINTS OF FURNACE VENT CONNECTOR. 3. PROVIDE A SEDIMENT TRAP ON GAS LINE @ FURNACE 4. DO NOT CUT THE PLUG OFF OF THE CONDENSATE PUMP CORD. FUSE STAT NOT REQUIRED. CONNECT OVERFLOW SENSOR ON PUMP & PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN. |
|
| 06/22/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ACCESS AT 2:30 PM FRIDAY |