Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07ME00417
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/10/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
07/27/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ELEC. CONDUIT IS NOT CONNECTED TO THE AC UNIT THE NUT ON THE INSIDE MAY HAVE COME OFF. 2. DISCONNECT IS OVERFUSED AT 60 AMP 45 AMP IS MAX FUSE SIZE 3. PROVIDE MORE SLOPE ON THE CONDENSATE DRAIN 1ST 10' IS FLAT |