Permit: T07ME00398

Parcel: 137292940

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/13/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/08/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE 1/8" PER FT. SLOPE ON CONDENSATE DRAIN
2. 3/8" I.D X 24" GAS FLEX NOT ADEQUATE FOR 96,000 BTU
FOR SHUT OFF VALVE MUST PRECEDE THE FLEX CONNECTOR. FLEX CONNECTOR FITTING ONLY HAND TIGHT.
3. DO NOT USE WHITE WIRE TO POWER THE AC UNIT
4. EXTEND CONDENSATE DOWN TO WITHIN 6" OF THE GROUND
5. PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPE