Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/08/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE 1/8" PER FT. SLOPE ON CONDENSATE DRAIN 2. 3/8" I.D X 24" GAS FLEX NOT ADEQUATE FOR 96,000 BTU FOR SHUT OFF VALVE MUST PRECEDE THE FLEX CONNECTOR. FLEX CONNECTOR FITTING ONLY HAND TIGHT. 3. DO NOT USE WHITE WIRE TO POWER THE AC UNIT 4. EXTEND CONDENSATE DOWN TO WITHIN 6" OF THE GROUND 5. PROVIDE A PRESSURE TEST ON ALL NEW GAS PIPE |