Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/04/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE PROPER DESCRIPTION OF WORK - AC UNIT WAS NOT REPLACED. - NEW COIL CONDENSOR & ELEC. CIRCUIT NEEDS TO BE ADDED TO PERMIT 2. VENT CONNECTOR NEEDS A REDUCER AT CONNECTION TO DOUBLE WALL. 3. PROVIDE A SEDIMENT TRAP ON GAS LINE AT FURNACE 4. CONDENSATE TRAP IS FLATTENED AT BOTTOM. REPLACE. 5. ISOLATE REFER LINE INSULATION & TAPE FROM VENT CONNECTOR. 6. TAPE BOTH ENDS OF WHITE WIRE WITH BLACK TAPE IN DISCONNECT & CIRCUIT PANEL |