Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAX FUSE SIZE 40 AMPS 2) ROMEX CANNOT BE RUN IN CONDUIT ALL THE WAY TO THE UNIT 3) INSTALL DRIP LEG ON GAS SUPPLY 4) PERMIT FOR ELECTRIC SERVICE UP GRADE ? |