Permit: T07ME00372

Parcel: 103214100

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/23/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
07/26/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
USE ANY OF THE HEATER KITS LABELED ON THE DATA PLATE
THERE IS NO ELEC. INFORMATION FOR A 3.6KW HEAT STRIP.
07/05/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CONDENSATE CANNOT TERMINATE ONTO THE NEIGHBORS PROPERTY. BE SURE TO SLOPE 1/8" PER FT.
2. MARK UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY
3. SECURE THE ELEC. DISCONNECT
06/20/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) A/C UNIT NEEDS TO BE IDENTIFIED-SINGLE OR SEPERATE-SO MAX FUSE CAN BE SIZED CORRECTLY
05/31/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
CONTACT NUMBER 248-8137 NO ANSWER
NO ACCESS TO SITE 9:20
WORK SHALL REMAIN ACCESSIBLE AND EXPOSED
FOR INSPECTION PURPOSES UNTIL APPROVED IN
ACCORDANCE WITH THE SECTION 109.1 IBC