Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PVC STILL NOT PAINTED. PROVIDED 1/8" PER FT. SLOPE CANVAS CONNECTOR NOT COVERED ADEQUATELY ON TOP & SIDE OF SUPPLY. RECALL FOR FINAL. |
|
| 06/06/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE A PERMIT & INSPECTION - INCLUDE A PETITION OF APPEAL. 2. DO A BETTER JOB COVERING THE CANVAS CONNECTORS 3. BLOCK & CLAMP PVC ON ROOF EVERY 4' PAINT W/LATEX 4. PROVIDE A SERVICE RECEPTACLE ON ROOF 5. 3/8" I.D X 36" GAS FLEX NOT ADEQUATE FOR 120,000 BTU 6. DO NOT USE WHITE WIRE FOR THE AC UNIT 7. PROVIDE THE PROPER DESCRIPTION OF WORK AND INCLUDE THE NEW ELEC. CIRCUIT TO THE AC UNIT. |