Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/28/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* FAILURE TO COMPLETE ALL ITEMS LISTED ON 6/19/09 WILL RESULT IN REFEE #1, #5 OVERFLOW SENSOR MUST BE IN SECONDARY DRAIN PORT SERVICE RECEPTACLE TO BE WEATHER RATED AND GFI PROTECTED. |
|
| 06/19/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE AN OVERFLOW SENSOR ON SECONDARY. IF USING PLASTIC BE SURE TO STAY AWAY FROM THE SINGLE WALL VENT CONNECTOR. 2. SEAL FRONT SIDE OF COIL ON FURNACE. 3. PROVIDE PROPER BLOCKING UNDER ELEC. CONDUIT & REFER LINE. 4. ALL LOW VOLTAGE WIRING MUST BE PROTECTED FROM PHYSICAL DAMAGE 5. DO NOT USE WHITE WIRES FOR AC UNIT. PROVIDE A SERVICE RECEPTACLE ON ROOF GFI. |
|
| 06/13/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LEVEL COMPRESSOR UNIT ON ROOF 2) SECURE BLOCKS HOLDING DISCONNECT TO ROOF 3) SECURE ELECTRIC WHIP TO UNIT 4) EVERYTHING INSIDE OK 5) INSTALL RAINTITE COVER ON OLD COOLER RECEPTACLE 6) CANNOT RUN ROMEX IN CONDUIT FOR OVER 2'. USE PROPER WIRE 7) PERMIT FOR ELECTRIC PANEL ? |