Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/11/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/10/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - SUPPORT GAS LINE ON ROOF EVERY 8' - 3/8" I.D FLEX IS NOT ADEQUATE FOR 100,000 BTU - PROVIDE A PERMIT FOR NEW WATER HEATER & NEW ELEC. CIRCUIT |
|
| 08/15/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection SUPPORT ELEC. CONDUIT AT SIDE OF PANEL. USE AN APPROVED FITTING ON LB & SEAL FITTING ABOVE BUSES. PROVIDE A GFI SERVICE RECEPTACLE ON ROOF 100,000 BTU FURNACE 100' FROM METER REQUIRES 3/4" PIPE DO NOT INCREASE 1/2" GAS PIPE TO 3/4" THE 3/4" MAIN LINE NOT ADEQUATE FOR BOTH APPLIANCES PAY A REINSPECTION FEE PRIOR TO NEXT INSPECTION. |