Permit: T07ME00351

Parcel: 133262060


Addresses:

409 N SARNOFF DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/11/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/10/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- SUPPORT GAS LINE ON ROOF EVERY 8'
- 3/8" I.D FLEX IS NOT ADEQUATE FOR 100,000 BTU
- PROVIDE A PERMIT FOR NEW WATER HEATER & NEW ELEC. CIRCUIT
08/15/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection

SUPPORT ELEC. CONDUIT AT SIDE OF PANEL. USE AN APPROVED FITTING ON LB & SEAL FITTING ABOVE BUSES.
PROVIDE A GFI SERVICE RECEPTACLE ON ROOF
100,000 BTU FURNACE 100' FROM METER REQUIRES 3/4" PIPE
DO NOT INCREASE 1/2" GAS PIPE TO 3/4"
THE 3/4" MAIN LINE NOT ADEQUATE FOR BOTH APPLIANCES
PAY A REINSPECTION FEE PRIOR TO NEXT INSPECTION.