Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. GAS FLEX CONNECTOR HAS NO LISTING ATTACHED. TYPICALLY A 3/8" I.D X 18" GAS FLEX IS NOT ADEQUATE FOR 96,000 BTU. CLAMP THE GAS LINE TO THE BLOCKS ON THE ROOF. 2. PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE. YOU CAN CONVERT THE OLD EVAP. COOLER CIRCUIT IF NECESSARY |