Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE OK FOR FINAL |
|
| 10/08/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE FRESH AIR INTAKES 2. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT YOU CAN TERMINATE DOWN TO A DIRT AREA OR INSIDE THE BLDG TO AN APPROVED LOCATION. PAINT EXPOSED PVC W/LATEX PAINT & BLOCK & CLAMP EVERY 4' 3. SECURE 1 ELEC. DISCONNECT 4. 3/8" I.D GAS FLEX NOT ADEQUATE FOR 100,000 BTU 5. REMOVE THE TRAP FROM CONDENSATE DRAIN AS PER INSTALL INSTRUCTIONS ON AC UNIT 6. PROVIDE A GFI SERVICE RECEPTACLE W/WATERPROOF BUBBLE TYPE COVER ON THE ROOF WITHIN 25' OF EQUIPMENT 7. PROVIDE REDWOOD SLEEPERS UNDER AC UNITS SPANNING THE ROOF JOISTS. |