Permit: T07ME00335

Parcel: 13103224H


Addresses:

5170 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/18/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
OK FOR FINAL
10/08/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE FRESH AIR INTAKES
2. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT
YOU CAN TERMINATE DOWN TO A DIRT AREA OR INSIDE THE BLDG TO AN APPROVED LOCATION. PAINT EXPOSED PVC W/LATEX PAINT & BLOCK & CLAMP EVERY 4'
3. SECURE 1 ELEC. DISCONNECT
4. 3/8" I.D GAS FLEX NOT ADEQUATE FOR 100,000 BTU
5. REMOVE THE TRAP FROM CONDENSATE DRAIN AS PER INSTALL INSTRUCTIONS ON AC UNIT
6. PROVIDE A GFI SERVICE RECEPTACLE W/WATERPROOF BUBBLE TYPE COVER ON THE ROOF WITHIN 25' OF EQUIPMENT
7. PROVIDE REDWOOD SLEEPERS UNDER AC UNITS SPANNING THE ROOF JOISTS.