Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07ME00320
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/01/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
05/31/2007 | MECHANICAL - FINAL | Denied | #15 FLEXIBLE GAS LINE MUST BE RIGIDLY SUPPORTED AGAINST MOVEMENT #9 - DISCONNECT ON ROOF MAY NOT HAVE A "HOT" WHITE WIRE. #10 - SELF EXPLANATORY |
|
05/17/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* DISCUSSED CORRECTIONS |
|
05/16/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE PROPER DESCRIPTION OF WORK 2. GAS LEAKING AT FLEX CONNECTOR ON ROOF. 3. SHUT OFF VALVE MUST PRECEDE THE FLEX CONNECTOR. 4. 3/8" I.D X 18" GAS FLEX NOT ADEQUATE FOR 120,000 BTU 5. SUPPORT THE GAS LINE ON THE ROOF CSST GAS PIPE 6. RUBBER COATING MUST EXTEND INTO THE FITTING ON THE ROOF. 7. SUPPORT CONDENSATE DRAIN EVERY 4' & PAINT WITH LATEX PAINT. 8. PROVIDE PROTECTION FROM GAS LINE SCRAPING ON SHARP METAL INSIDE CLOSET AT PENETRATION THRU THE CEILING. 9. DO NOT USE WHITE WIRE AS A CONDUCTOR FOR THE AC UNIT. 10. PROVIDE A GFI SERVICE RECEPTACLE ON ROOF. 11. INSULATE ALL EXPOSED SHEETMETAL DUCT IN THE ATTIC. 12. SUPPORT GAS LINE IN ATTIC 13. PROVIDE R8 DUCT LINER ON ROOF |
|
05/10/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* NO ONE HOME NO PHONE MESSAGE WILL NEED TO HAVE LADDER FOR ROOF ACCESS |