Permit: T07ME00320

Parcel: 122060720


Addresses:

4207 E WAVERLY ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07ME00320

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/01/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
05/31/2007 MECHANICAL - FINAL Denied #15 FLEXIBLE GAS LINE MUST BE RIGIDLY SUPPORTED AGAINST MOVEMENT

#9 - DISCONNECT ON ROOF MAY NOT HAVE A "HOT" WHITE WIRE.

#10 - SELF EXPLANATORY
05/17/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
DISCUSSED CORRECTIONS
05/16/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE PROPER DESCRIPTION OF WORK
2. GAS LEAKING AT FLEX CONNECTOR ON ROOF.
3. SHUT OFF VALVE MUST PRECEDE THE FLEX CONNECTOR.
4. 3/8" I.D X 18" GAS FLEX NOT ADEQUATE FOR 120,000 BTU
5. SUPPORT THE GAS LINE ON THE ROOF CSST GAS PIPE
6. RUBBER COATING MUST EXTEND INTO THE FITTING ON THE ROOF.
7. SUPPORT CONDENSATE DRAIN EVERY 4' & PAINT WITH LATEX PAINT.
8. PROVIDE PROTECTION FROM GAS LINE SCRAPING ON SHARP METAL INSIDE CLOSET AT PENETRATION THRU THE CEILING.
9. DO NOT USE WHITE WIRE AS A CONDUCTOR FOR THE AC UNIT.
10. PROVIDE A GFI SERVICE RECEPTACLE ON ROOF.
11. INSULATE ALL EXPOSED SHEETMETAL DUCT IN THE ATTIC.
12. SUPPORT GAS LINE IN ATTIC
13. PROVIDE R8 DUCT LINER ON ROOF
05/10/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
NO ONE HOME
NO PHONE MESSAGE
WILL NEED TO HAVE LADDER FOR ROOF ACCESS