Permit: T07ME00318

Parcel: 128140030


Addresses:

517 S ROSEMONT AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/27/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
07/06/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
GAS FLEX STILL NOT ADEQUATE
CONDENSATE STILL NOT SLOPED 1/8" PER FT
05/15/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 3/8" I.D X 36" GAS FLEX CONNECTOR NOT ADEQUATE
FOR 120,000 BTU.
2. BLOCK & CLAMP CONDENSATE DRAIN EVERY 4' AND PAINT WITH LATEX PAINT & PROVIDE MIN. 1/8" PER FT. SLOPE.
SECURE TO THE SIDE OF THE HOUSE. TERMINATE WITHIN 6" OF THE GROUND WITH AN ELBOW & NIPPLE. DIVERT THE WATER AWAY FROM THE HOUSE.
3. PROVIDE A GFI SERVICE RECEPTACLE ON THE ROOF WITH A WATERPROOF COVER AS PER N.E.C
4. NEED TO SEE CIRCUIT BREAKER.