Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2011 | MECHANICAL - FINAL | Approved | ||
| 05/14/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PLEASE PROVIDE A SERVICE RECEPTACLE ON ROOFTOP 2. PROVIDE MIN. 1/8" PER FT. SLOPE ON CONDENSATE DRAIN. 3. LOW VOLTAGE CONDUIT NOT CONNECTED TO A/C UNIT PROPERLY. TIGHTEN ALL LOOSE FITTINGS. RECALL FOR FINAL ALSO, RELOCATE THE GAS LINE BLOCKING THE SERVICE PANEL |