Permit: T07ME00316

Parcel: 133368700


Addresses:

10015 E LORIAN ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/04/2011 MECHANICAL - FINAL Approved
05/14/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PLEASE PROVIDE A SERVICE RECEPTACLE ON ROOFTOP
2. PROVIDE MIN. 1/8" PER FT. SLOPE ON CONDENSATE DRAIN.
3. LOW VOLTAGE CONDUIT NOT CONNECTED TO A/C UNIT PROPERLY. TIGHTEN ALL LOOSE FITTINGS.

RECALL FOR FINAL

ALSO, RELOCATE THE GAS LINE BLOCKING THE SERVICE PANEL